GMA 41/GMA 44控制器
l Easy mounting on DIN-rail
l State-of-the-art microprocessor technology
l Flexible, for all measuring tasks
l For 1 to 4 transmitters
l Can also be configured at a later stage
Fixed systems gas warning for DIN-rail mounting:
The GMA 41, one channel gas warning system, and the 4-channel device GMA 44 together with the efficient and robust transmitters of GfG offer safe and reliable gas warning systems.
Alarm thresholds:
Both systems have three alarm levels. Every alarm can be adjusted separay. False alarms are eliminated with the adjustable alarm delay. The threshold values can be freely adjusted within the detection range. They can also be adjusted at a later stage with the control keys to adapt to changing requirements. Every threshold value can be selected to be latching/non-latching and resettable/non-resettable.
Alarm relaying:
Every controller provides 4 voltage-free relays for the three alarms and the fault warning. The relays may be used to control external alarm devices like lamps or horns. They even can introduce specific counter measures to prevent or limit dangers from gases or vapours.
Additional Features:
The GMA 41 and GMA 44 store minimum and peak values and therefore after an alarm, the gas danger can exactly be determined. With the help of the key-operated switch, all connected GMA's can be switched to a collective alarm. The GMA (variant B) offers an integrated Bus-system. The Bus-system transfers alarms and malfunctions for a collective alarm and establishes the connection of the power supply for all GMA´s. Several GMA´s can simply be connected without any additional wiring required.
EC versions are integrated with a transformer for 230 V voltage supply. The GMA EC with high voltage can effectively operate all transmitters with electrochemical sensors. The ECB version takes the multiple technology from the integrated transformer with the bus system to create
a dynamic sensor that still supplies a 230 V voltage.
GMA 41/44:
Gases
depending on transmitter:
combustible/explosive, toxic gases
and vapors, oxygen
Detection range
depending on requirements:
% LEL, Vol %, ppm, mg/m3
Ambient temperature
-20 .. + 50ºC
(-4 to +122ºF)
Power supply
24 V DC, 230 V (GMA 41EC/44EC)
Power consumption
Max. 4 W, normal 2 W
Input signal
0,2 .. 1 mA / 4 .. 20 mA
Output signal
Linear signal 4 .. 20mA (GMA 41)
Dimensions
106 x 90 x 58 mm (HxD)
(4.24 x 3.6 x 2.32 inches)
Calibration
Automatic zeroing, calibration with data
logging
Alarms
3 Alarm thresholds, freely adjustable within
the detection range
Alarm functions
Exceeding / falling short,
latching / non-latching,
resettable / non-resettable,
hysteresis adjustable,
delay-time 0 .. 2 minutes,
alarm thresholds compley adjustable,
alarm allocation by GMA 44
Relay outputs
4 voltage-free relays for alarm and fault,
normally closed contact (NC), normally
open contact (NO), change-over contacts.
Load: 1000 VA, 5 A
Display
3-digit LED display for linear measurement
values, Service
1 LED green - operational status
1 LED yellow - fault
3 LEDs red - alarm
display of maximum/minimum values
Function keys
4 different keys for all functions, like alarm
thresholds, calibration, function test and
relay test
Function test
PFG No. 41300500
Models
GMA 41/GMA 44
Power supply 24 V
GMA 41 B/GMA 44 B
Bus system, power supply 24 V
GMA 41 EC/GMA 44 EC
Power supply 230 V, for operation of
electrochemical sensor with 0,2 .. 1 mA
signal output
GMA 41 ECB/GMA 44 ECB
Power supply 230 V, for operation of
electrochemical sensor with 0,2 .. 1 mA
signal output, bus system
Key-operated switch
GMA 41/GMA 44 SW (24 V)
GMA 41/GMA 44 SW (230 V)
Power Supply Module
PS 12 (12 W)
PS 30 (30 W)
PS 50 (50 W