Schmersal SRB-206SQ安全开关
时间:2018-12-05 阅读:426
• Multi-evaluation of up to 6 safety guards
• Suitable for signal processing of potential-free outputs, e.g. emergency stop command devices, position switches and solenoid interlocks
• 2 safety contacts, STOP 0
• 6 Signalling outputs
Ordering details | |
Product type description | SRB 206SQ-24V |
Article number | 101173934 |
EAN Code | 4250116201877 |
eCl@ss | 27-37-19-01 |
Classification | |
Standards | EN ISO 13849-1, IEC 61508, EN 60947-5-1 |
PL | bis d (STOP 0) |
Control category | bis 3 (STOP 0) |
DC | > 60% (STOP 0) |
CCF | > 65 points |
PFH value | ≤ 2,0 x 10-7/h (STOP 0) |
SIL | bis 2 (STOP 0) |
Mission time | 20 Years |
- notice | The PFH value is applicable for the combinations listed in the table for contact load (K) (current through enabling paths) and switching cycle number (n-op/y). In case of 365 operating days per year and a 24-hour operation, this results in the specified switching cycle times (t-cycle) for the relay contacts. Diverging applications on request. |
Global Properties | |
Permanent light | SRB206SQ |
Standards | IEC/EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508 |
Compliance with the Directives (Y/N) | Yes |
Climatic stress | EN 60068-2-78 |
Mounting | snaps onto standard DIN rail to EN 60715 |
Terminal designations | IEC/EN 60947-1 |
Materials | |
- Material of the housings | Plastic, glass-fibre reinforced thermoplastic, ventilated |
- Material of the contacts | AgCdO, self-cleaning, positive action |
Weight | 400 |
Start conditions | Automatic or Start button (Optional monitored) |
Start input (Y/N) | Yes |
Feedback circuit (Y/N) | Yes |
Start-up test (Y/N) | No |
Reset after disconnection of supply voltage (Y/N) | Yes |
Automatic reset function (Y/N) | Yes |
Reset with edge detection (Y/N) | Yes |
Pull-in delay | |
- ON delay with reset button | typ. 50 ms |
Drop-out delay | |
- Drop-out delay in case of emergency stop | ≤ 30 ms |
Mechanical data | |
Connection type | Screw connection |
Cable section | |
- Min. Cable section | 0,25 |
- Max. Cable section | 2.5 |
Pre-wired cable | rigid or flexible |
Tightening torque for the terminals | 0,6 |
Detachable terminals (Y/N) | Yes |
Mechanical life | 10.000.000 operations |
Electrical lifetime | Derating curve available on request |
restistance to shock | 30 g / 11 ms |
Resistance to vibration To EN 60068-2-6 | 10…55 HZ, Amplitude 0,35 mm, ± 15 % |
Ambient conditions | |
Ambient temperature | |
- Min. environmental temperature | −25 °C |
- Max. environmental temperature | +45 °C |
Storage and transport temperature | |
- Min. Storage and transport temperature | −40 °C |
- Max. Storage and transport temperature | +85 °C |
Protection class | |
- Protection class-Enclosure | IP40 |
- Protection class-Terminals | IP20 |
- Protection class-Clearance | IP54 |
Air clearances and creepage distances To IEC/EN 60664-1 | |
- Rated impulse withstand voltage Uimp | 4 kV |
- Overvoltage category | III To VDE 0110 |
- Degree of pollution | 2 To IEC/EN 60664-1 |
Electromagnetic compatibility (EMC) | |
EMC rating | conforming to EMC Directive |
Electrical data | |
Rated DC voltage for controls | |
- Max. rated DC voltage for controls | 20.4 |
- Max. rated DC voltage for controls | 28.8 |
Rated AC voltage for controls, 50 Hz | |
- Min. rated AC voltage for controls, 50 Hz | 20.4 |
- Max. rated AC voltage for controls, 50 Hz | 26.4 |
Rated AC voltage for controls, 60 Hz | |
- Min. rated AC voltage for controls, 60 Hz | 20.4 |
- Max. rated AC voltage for controls, 60 Hz | 26.4 |
Contact resistance | max. 100 mΩ |
Power consumption | 3.6 W; 6.6 VA plus signalling outputs Y1-Y6 |
Type of actuation | AC/DC |
Rated operating voltage Ue | 24 VDC −15% / +20%, residual ripple max. 10% 24 VAC −15% / +10% |
Operating current Ie | 0,275 A |
Frequency range | 50 / 60 HZ |
Electronic protection (Y/N) | Yes |
Fuse rating for the operating voltage | Internal electronic trip, tripping current > 1 A, Reset after disconnection of supply voltage |
Inputs | |
Monitored inputs | |
- Short-circuit recognition (Y/N) | Yes |
- Wire breakage detection (Y/N) | Yes |
- Earth connection detection (Y/N) | Yes |
Number of shutters | 0 piece |
Number of openers | 12 piece |
Cable length | 1500 m with 1.5 mm²; 2500 m with 2.5 mm² |
Conduction resistance | max. 40 Ω |
Outputs | |
Stop category | 0 |
Number of safety contacts | 2 piece |
Number of auxiliary contacts | 0 piece |
Number of signalling outputs | 6 piece |
Switching capacity | |
- Switching capacity of the safety contacts | max. 230 VAC, 6 A ohmic (inductive in case of appropriate protective wiring) |
- Switching capacity of the auxiliary contacts | 24 VDC, 2 A |
- Switching capacity of the signaling/diagnostic outputs | Y1…Y6: 24 VDC, 20 mA (externally through A1.1) |
Fuse rating | |
- Protection of the safety contacts | 6.3 A slow blow |
- Fuse rating for the signaling/diagnostic outputs | 200 mA slow blow |
Utilisation category To EN 60947-5-1 | AC-15: 230 V / 6 A DC-13: 24 V / 6 A |
Number of undelayed semi-conductor outputs with signaling function | 0 piece |
Number of undelayed outputs with signaling function (with contact) | 6 piece |
Number of delayed semi-conductor outputs with signaling function. | 0 piece |
Number of delayed outputs with signalling function (with contact). | 0 piece |
Number of secure undelayed semi-conductor outputs with signaling function | 0 piece |
Number of secure, undelayed outputs with signaling function, with contact. | 2 piece |
Number of secure, delayed semi-conductor outputs with signaling function | 0 piece |
Number of secure, delayed outputs with signaling function (with contact). | 0 piece |
LED switching conditions display | |
LED switching conditions display (Y/N) | Yes |
Number of LED´s | 4 |
LED switching conditions display | |
- The integrated LEDs indicate the following operating states. | |
- Position relay K2 | |
- Position relay K1 | |
- Supply voltage | |
- Internal operating voltage Ui | |
Miscellaneous data | |
Applications | Emergency-Stop button Pull-wire emergency stop switches Guard system |
Dimensions | |
Dimensions | |
- Width | 45 mm |
- Height | 100 mm |
- Depth | 121 mm |
notice | |
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. | |
notice - Wiring example | |
Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R); cross-wire monitoring and feedback circuit (H2) | |
If more guard doors are monitored, they must be connected according to the wiring table | |
The control recognises cross-short, cable break and earth leakages in the monitoring circuit. | |
Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. | |
A single failure in the sensors does not cause the safety to be lost | |
If the single failure occurs, the safety function will be maintained. Some, although not all, errors will be recognised. An accumulation of unrecognised errors could cause the safety function to be lost. | |
Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X3. If the feedback circuit is not required, establish a bridge | |
The wiring diagram is shown with guard doors closed and in de-energised condition. | |
K.A. Schmersal GmbH & Co. KG, Möddinghofe 30, D-42279 Wuppertal The data and values have been checked throroughly. Technical modifications and errors excepted. Generiert am 03.12.2018 - 02:42:13h Kasbase 3.3.0.F.64I |