YDJ-5kVA/50kV交流试验变压器技术参数
时间:2022-06-22 阅读:919
YDJ-5kVA/50kV交流试验变压器技术参数:
型号 | 容量 (KVA) | 高压输出 电压(KV) | 高压输出 电流(mA) | 低压输入 | 变比 | 温升℃ 30分钟 | |
V | A | ||||||
YDJ -1.5 | 1.5 | 50 | 30 | 200 | 7.5 | 500 | 10 |
YDJ -3 | 3 | 50 | 60 | 200 | 15 | 500 | 10 |
YDJ -5 | 5 | 50 | 100 | 200 | 25 | 500 | 10 |
YDJ -10 | 10 | 50 | 200 | 220/380 | 50/26 | 500 | 10 |
YDJ -15 | 15 | 50 | 300 | 380 | 37.5 | 500 | 10 |
YDJ -20 | 20 | 50 | 400 | 380 | 53 | 500 | 10 |
YDJ -30 | 30 | 50 | 600 | 380 | 79 | 500 | 10 |
YDJ -40 | 40 | 50 | 800 | 380 | 105 | 500 | 10 |
YDJ -50 | 50 | 50 | 1000 | 380 | 132 | 500 | 10 |
YDJ -5 | 5 | 100 | 50 | 200 | 25 | 1000 | 10 |
YDJ -10 | 10 | 100 | 100 | 200/380 | 50/26 | 1000 | 10 |
YDJ -20 | 20 | 100 | 200 | 380 | 53 | 1000 | 10 |
YDJ -30 | 30 | 100 | 300 | 380 | 79 | 1000 | 10 |
YDJ -40 | 40 | 10 | 400 | 380 | 105 | 1000 | 10 |
YDJ -50 | 50 | 100 | 500 | 380 | 132 | 1000 | 10 |
YDJ -100 | 100 | 100 | 100 | 500 | 263 | 1000 | 10 |
YDJ -150 | 150 | 100 | 1500 | 500 | 300 | 1000 | 10 |
YDJ -200 | 200 | 100 | 2000 | 500 | 400 | 1000 | 10 |
YDJ -250 | 250 | 100 | 2500 | 380 | 500 | 1000 | 10 |
YDJ -20 | 20 | 150 | 133 | 380 | 53 | 1500 | 10 |
YDJ -30 | 30 | 150 | 200 | 380 | 79 | 1500 | 10 |
YDJ -50 | 50 | 150 | 333 | 380 | 132 | 1500 | 10 |
YDJ -100 | 100 | 150 | 666 | 500 | 263 | 1500 | 10 |
YDJ -150 | 150 | 150 | 1000 | 500 | 300 | 1500 | 10 |
YDJ -200 | 200 | 150 | 1333 | 500 | 400 | 1500 | 10 |
说明:
2.1做直流泄漏与直流耐压试验时,只能使用YDJ (JZ)试变,且在使用时必须将高压硅堆接在实验变压器均压球上。
2.2做电缆耐压不需另并电容,可用分压器,分压器更直观,准确读出高压电压值。
2.3做直流泄漏时,微安表可直接读出直流泄漏值。
2.4直流泄漏完成后,可不拆线直接进行直流耐压试验。
2.5做避雷器试验时需加电容。
3.串激组合试变接线
3.1交流系列高压试变,可将几台YDJ (G)YDJ-5kVA/50kV交流试验变压器通过适当的组合形成电压*的试验变压器。其原理是在YDJ (G)高压绕组中绕激磁绕组,该绕组和后一级试变初级线圈参数相同。