YJV-6/6千伏电缆YJV22-6/10千伏高压电缆
6kV~35kV 中低压铜芯及铝芯交联聚乙烯绝缘电力电缆(YJV电缆,YJV22电缆,YJLV电缆,YJLV22电缆)XLPE Insulated Power Cable |
交联聚乙烯绝缘电力电缆是采用化学方法或物理方法,使聚乙烯分子由线型分子结构转变为三维网状结构,由热塑性的聚乙烯变成热固性的交联聚乙烯,从而提高了聚乙烯的耐老化性能、机械性能和耐环境能力,并保持了优良的电气性能。 交联聚乙烯绝缘电力电缆导体的允许长期zui高温为90摄氏度,较低绝缘电缆、聚氯乙烯绝缘电缆和聚乙烯绝缘电缆高,且具有重量轻、结构简单、使用方便、耐化学腐蚀和敷设不受落差限制等优点。 26/35KV电力电缆,18/30KV交联电缆,12/20KVYJV电缆,8.7/15KVYJV22电缆线,6/10KV铝芯交联电缆线,3.6/6KVYJLV单芯电缆 中低压交联电缆产品标准 Standard 本产品按GB12706《额定电压35V及以下铜芯、铝芯塑料绝缘电力电缆》标准生产,同时还可根据用户需要按电工委员会推荐标准IEC、英国标准、德国标准及美国标准生产。 The product is manufactured according to the standard of《GB12706 or IEC、BS、DIN and ICEA upon request. 适用范围 Applications YJV-6/6千伏电缆YJV22-6/10千伏高压电缆 本产品适用于工频额定电压3.6/6kv~26/35kv输配电线路作配送电能子用。 The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv. 使用特性 Operating characteristics · 工频额定电压U0/U为3.6/6kv~26/35kv。 Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv. · 电缆导体的zui高允许工作温度:90℃。 Max.admissible operating temperature of the conductor:90℃. · 短路时(zui长时间不超过5s)电缆导体的zui高温度不超过2500C。 Max. short-circurt temperature of conductor shall not exceed 2500C. (5s maximum duration) · 电缆敷设时环境温度应不低于00C。 The ambient temperature under installation should not below 00C. · 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。 The bending radius of a single-core cable should not less than 20 times of the cable diameter. The bending radius of a single-core cable should not less than 15 times of the cable diameter. 电缆额定电压的选择 Voltage designation · 电缆的额定电压应适合于电缆系统的运行状况,用U0/U(Um)kv表示。 U0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压; U-电缆设计用的导体间的额定工频电压; Um-设备可承受的“zui高系统电压”的zui大值。 The rated voltage of the cable for a given applixation shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of U0/U(Um)kv Where: U0-The rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed; U - The rated power-frequency voltage between conductos, for which the cable designed; Um- The maximum value of the“highest system voltage”for which the equipment may beused. · 三相系统用电缆的U0值推荐如下表: The values of U0 recommened for cable to be used in three-phase systems are listed below: |
U kv | U m kv | U 0 * kv | A 和 B 类系统 System categories A and B | C 类系统 Systems categories C | 6 | 7.2 | 3.6 | 6 | 10 | 12 | 6 | 8.7 | 15 | 17.5 | 8.7 | 12 | 20 | 24 | 12 | 18 | 30 | 36 | 18 | - | 35 | 40.5 | 21 | 26 |
|
A类系统──该类系统任何一相导体与地和接地导体接触时,能在1min内与系统分离 B类系统──该类系统仅包括单相接地故障短时运行的条件,接地故障时间应不超过1h, 但在任何情况下,zui长不超过8h每年接地故障总持续时间不超过125h; C类系统──不属于A类、B类的系统。 System category A──This category comprises those systems in which any phase conductor that comes in contact with earth or an earth conductor. is disconnected from the system within 1 min. System category B ──This category comprises those system which,under faultconditions,are operated,are operated for ashorttimewith one phase earthed.This period should not exceed 1 h..Fora longer period, not exceeding 8h on any occasion, can be tolerated.The total duration of earth faults in any year should not exceed 125h. System categeory C──This category comprises all systems which do not fall into A and B 电缆的型号Type of cable |
型号 Type | 名称 Designation | 适用范围 Application | YJV | 铜芯交联聚乙烯绝缘氯乙烯护套电力电缆 Copper conductor,XLPE insulated and PVC sheathed power cable | 室内、隧道及电缆沟等场所,不能承受机械外力。单芯电缆不允许敷设在磁性管道中。 For laying indoors 、 intunnel or cable trench,unable to bear external mechan-icalforces.Single-core cable in magnetic duct is not permissible | YJLY | 铝芯交联聚乙烯绝缘乙烯护套电力电缆 Aluminium conductor, XLPE insulated and PVC sheathed power cable | YJY | 铜芯交联聚乙烯绝缘氯乙烯护套电力电缆 Copper conductor ,XLPE insulated and PEsheathed power cable | YJLY | 铝芯交联聚乙烯绝缘氯乙烯护套电力电缆 Alumimium conductor ,XLPE |
|
产品介绍:高压交联电缆产品具有传输容量大,工作温度,不受落差的限制,安装敷设方便等特点,广泛应用于工矿企业和城市电网中。高压交联电缆主要用于电力、建筑、工矿、冶金、交通等部门的动力、照明输配电系统,由于聚乙烯是电绝缘性能的塑料,加上经过高分子交联后成为热固性材料,因此其电性能好,机械性能和耐热性好。近二十年来,已成为中国中、高压电缆的主导品种,产品适用于6——35KV的各个电压级中它可分为:YJV-交联聚乙稀绝缘聚氯乙烯护套电力电缆,YJV22-交联聚乙烯绝缘钢带铠装高压电缆,YJLV-交联聚乙烯绝缘铝芯钢带铠装高压电缆。
执行标准:GB/T12706-2002
使用特性
· 工频额定电压U0/U为6kv/10kv~26/35kv。
· 电缆导体的zui高允许工作温度:90℃。
· 短路时(zui长时间不超过5s)电缆导体的zui高温度不超过2500C。
· 电缆敷设时环境温度应不低于00C。
· 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。
电缆额定电压的选择
· 电缆的额定电压应适合于电缆系统的运行状况,用U0/U(Um)kv表示。
U0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压;
U-电缆设计用的导体间的额定工频电压;
Um-设备可承受的“zui高系统电压”的zui大值。
防火防爆
发电厂、变电站及工矿企业都大量使用电力电缆,一旦电缆起火爆炸,将会引起严重火灾和停电事故,此外,电缆燃烧时产生大量浓烟和毒气,不仅污染环境,而且危及人的生命安全。为此,应注意电力电缆的防火。
电缆爆炸起火的原因
电力电缆的绝缘层是由纸、油、麻、橡胶、塑料、沥青等各种可燃物质组成,因此,电缆具有起火爆炸的可能性。导致电缆起火爆炸的原因是:
(1)绝缘损坏引起短路故障。电力电缆的保护铅皮在敷设时被损坏或在运行中电缆绝缘受机械损伤,引起电缆相间或铅皮间的绝缘击穿,产生的电弧使绝缘材料及电缆外保护层材料燃烧起火。
(2)电缆长时间过载运行。长时间的过载运行,电缆绝缘材料的运行温度超过正常发热的zui高允许温度,使电缆的绝缘老化干枯,这种绝缘老化干枯的现象,通常发生在整个电缆线路上。由于电缆绝缘老化干枯,使绝缘材料失去或降低绝缘性能和机械性能,因而容易发生击穿着火燃烧,甚至沿电缆整个长度多处同时发生燃烧起火。
(3)油浸电缆因高差发生淌、漏油。当油浸电缆敷设高差较大时,可能发生电缆淌油现象。淌流的结果,使电缆上部由于油的流失而干枯,这部分电缆的热阻增加,使纸绝缘焦化而提前击穿。另外,由于上部的油向下淌,在上部电缆头处腾出空间并产生负压力,使电缆易于吸收潮气而使端部受潮。电缆下部由于油的积聚而产生很大的静压力,促使电缆头漏油。电缆受潮及漏油都增大了发生故障起火的机率。