设备振动安全保护报警箱
设备振动安全保护报警箱

PMX1500设备振动安全保护报警箱

参考价: 面议

具体成交价以合同协议为准
2024-11-21 13:26:00
561
产品资料:
查看PDF文档

产品属性
关闭
长祥激振科技(上海)有限公司

长祥激振科技(上海)有限公司

高级会员1
收藏

组合推荐相似产品

产品简介

设备振动安全保护报警箱,CTC振动加速度传感器可以用于关键旋转设备的振动安全保护。自带继电器输出和显示屏,实时显示所监测设备的振动量级值,用户也可以根据自己的实际情况输入振动报警阈值,来触发一个继电器输出,从而切断设备的运行,以防止危险发生。

详细介绍

设备振动安全保护报警箱

设备振动安全保护报警箱

设备振动安全保护报警箱

设备振动安全保护报警箱

Example: Full Scale 0.00 – 1.00 IPS, Frequency Band 10 – 1000 Hz At 0 .00 IPS, 4 mA flows from the transmitter to the controller . At 0 .50 IPS,  12 m flows from the transmitter to the controller . At 1 .00 IPS, 20 mA flows from the transmitter to the controller . The monitoring channel provides two relay outputs . The system comes from the factory with a specific vibration range in IPS or mm/s . This range must be known to configure the relay set points . It is recommended that baseline and typical alarm values of vibration are also known before setup is attempted . The relays provided by the internal controller are highly configurable . Refer to the PD765 user manual for detailed programming instructions . All of the following parameters can be adjusted: • Relay Action – Automatic, Latching, Auto + Manual Reset, Latch with Clear • Relay Operation – Set and Reset points (Hysteresis), On and Off time Delays

 

Example Setup 1: A full-scale range of 0 .00 – 1 .00 IPS has been specified . The baseline vibration on the machine to be monitored is 0 .18 IPS-pk . Alarm and shutdown levels of vibration are defined as 0 .35 IPS-pk and 0 .65 IPS-pk, respectively . Reset points are specified as 0 .30 IPS-pk and 0 .60 IPS-pk . Using the provided PD765 Process Controller manual, select the relay operation and action desired . For this example, we will have LOC, Latching Operation with Clear relays . Then program “Set 1” as 0 .35 and “Set 2” as 0 .65, then program reset points, “rST 1” as 0 .30 and “rST 2” as 0 .60 . After relays have been programmed, scaling must be set . For this example, we will use a 4 - 20 mA input with a 0 .00 - 1 .00 IPS display . Program “inP1” as 4 .00, then “diS1” as 0 .00, then “inP2” as 20 .00, then “diS2” as 1 .00 . This will create an input of 4 mA, display of 0 .00 IPS, and at an input of 20 mA,  1 .00 IPS will be displayed by the meter . The system will now actuate the LOC Relay (Relay 1) when the vibration level reaches 0 .35 IPS-pk and another  13LOC Relay (Relay 2) when the vibration level reaches 0 .65 IPS-pk . To reset the LOC relays, the vibration level must fall below the reset point of 0 .60, then press the ACK for relay two . Once the vibration level falls below 0 .30, press the ACK to reset Relay 1 .

上一篇:选择合适的振动传感器:综合指南 下一篇:CTC传感器齿轮箱损坏监测
热线电话 在线询价
提示

请选择您要拨打的电话:

当前客户在线交流已关闭
请电话联系他 :